No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o1-14
(3106)
Frequency Reference
and Frequency Related
Monitor Custom Units 2
Fref Cust Unit 2
Sets the customer-specified unit display for the frequency
reference parameters and frequency related monitors when
o1-03 = 3 and o1-09 = 15 as custom units
Default: 41
Range: 30 to 7A
o1-15
(3107)
Frequency Reference
and Frequency Related
Monitor Custom Units 3
Fref Cust Unit 3
Sets the customer-specified unit display for the frequency
reference parameters and frequency related monitors when
o1-03 = 3 and o1-09 = 15 as custom units
Default: 41
Range: 30 to 7A
o1-16
(3108)
F1 Key Function
Selection
F1 Key Func Sel
0: Standard
1: Mon
2: DRV/BYP
3: RUN BYP
4: RLY
Selects the function of the F1 key and the LCD display text
above the F1 key.
0: Standard
1: Monitor
2: Drive/Bypass (DRV/BYP)
3: Bypass Run Command (RUN BYP)
4: Toggle Relay Output (RLY)
Default: 0
Range: 0 to 4
o1-17
(3109)
F2 Key Function
Selection
F2 Key Func Sel
0: Standard
1: Mon
2: DRV/BYP
3: RUN BYP
4: RLY
Selects the function of the F1 key and the LCD display text
above the F1 key.
0: Standard
1: Monitor
2: Drive/Bypass (DRV/BYP)
3: Bypass Run Command (RUN BYP)
4: Toggle Relay Output (RLY)
Default: 0
Range: 0 to 4
o1-18
(310A)
User Defined Parameter
Upper
Userdefined par1
Allows the user to set values that can be used as reference
information.
Default: 0
Range: 0 to 999
o1-19
(310B)
User Defined Parameter
Lower
Userdefined par2
Allows the user to set values that can be used as reference
information.
Default: 0
Range: 0 to 999
<1> Default is 1 when b5-01 is set to 0.
Default is 3 when b5-01 is set to 1 or 3.
<2> Default is 0 when b5-01 is set to 0.
Default is 1 when b5-01 is set to 1 or 3.
<3> Default is 102 when b5-01 is set to 0.
Default is 504 when b5-01 is set to 1 or 3.
<4> Default is 102 when b5-01 is set to 0.
Default is 501 when b5-01 is set to 1 or 3.
<5> Default setting is dependent on parameter o1-03, HOA Keypad Display Selection.
u
o2: HOA Keypad Functions
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
o2-02
(0506)
OFF Key Function
Selection
Oper STOP Key
0: Disabled
1: Enabled
0: Disabled. OFF key is disabled in REMOTE operation.
1: Enabled. OFF key is always enabled.
Default: 1
Range: 0, 1
o2-03
(0507)
User Parameter Default
Value
User Default Sel
0: No Change
1: Save User Init
2: Clear User Init
0: No change.
1: Set defaults. Saves parameter settings as default values for a
User Initialization.
2: Clear all. Clears the default settings that have been saved for
a User Initialization.
Default: 0
Range: 0 to 2
o2-04
(0508)
Drive Model Selection
Inverter Model #
Enter the drive model. Setting required only if installing a new
control board.
Default:
Determined by
drive capacity
o2-05
(0509)
Frequency Reference
Setting Method
Selection
Oper Ref Method
0: Disabled
1: Enabled
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be
adjusted using the up and down arrow keys only.
Default: 0
Range: 0, 1
o2-06
(050A)
Operation Selection
when HOA Keypad is
Disconnected
Oper Discon Det
0: Disabled
1: Enabled
0: The drive continues operating if the HOA keypad is
disconnected.
1: An oPr fault is triggered and the motor coasts to stop.
Default: 1
Range: 0, 1
o2-07
(0527)
Motor Direction at
Power Up when Using
Operator
For/RevSel@PwrUp
0: Forward
1: Reverse
0: Forward
1: Reverse
This parameter requires assigning drive operation to the HOA
keypad.
Default: 0
Range: 0, 1
A.12 o: Operator-Related Settings
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
237
A
Parameter List