Automatic Offset Adjustment of Motor Current Detection Signals
Use the following procedure to adjust the offset of the motor current detection signals for a multi-winding drive system.
After you complete the adjustment, always disable automatic adjustment (Pn009 = n.
0).
Note: Perform this adjustment only the first time that the main circuit power supply is turned ON after the control power
supply is turned ON.
Related Parameters
4.2.2
Subcommands
The following table lists the subcommands for MECHATROLINK-II communications.
Step
Operation
1
Enable automatic adjustment of the motor current detection signal offset (Pn009 = n.
1).
2
Turn the control power supply OFF and ON again.
3
Turn the SERVOPACK/converter main circuit power supplies OFF and ON again.
The motor current detection signal offset will be automatically adjusted when the main circuit power supplies
to the SERVOPACKs are detected.
Up to 2 seconds will be required for the automatic adjustment.
4
Disable automatic adjustment of the motor current detection signal offset (Pn009 = n.
0).
Parameter
Meaning
When Enabled
Pn009
n.
0
[Factory
setting]
Does not execute automatic adjustment.
After restart
n.
1
Performs automatic offset signal adjustment of the motor current
detection signal when the main circuit power supply is turned ON.
Command
Code
Command
Function
00 hex
NOP
Same function as NOP main command.
01 hex
PRM_RD
Same function as PRM_RD main command.
02 hex
PRM_WR
Same function as PRM_WR main command.
05 hex
ALM_RD
Same function as ALM_RD main command.
1C hex
PPRM_WR
Same function as PPRM_WR main command.
28 hex
LTMOD_ON
Same function as LTMOD_ON main command.
29 hex
LTMOD_OFF
Same function as LTMOD_OFF main command.
30 hex
SMON
Same function as SMON main command.