8.4 Installing Peripheral Devices
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
211
Pe
ri
ph
er
al
D
evi
c
es
&
Opt
ions
8
n
Connecting an AC Reactor
Figure 8.4
Figure 8.4 Connecting an AC Reactor
n
Connecting a DC Reactor
When installing a DC reactor, remove the jumper between ter1 and +2 (terminals are jumpered for shipment).
The jumper must be installed if not using a DC reactor. Refer to
for an example of DC reactor wiring.
Figure 8.5
Figure 8.5 Connecting a DC Reactor
u
Connecting a Noise Filter
n
Reducing Radiated, Conducted, and Induced Noise
Drives generate noise that can potentially affect surrounding devices like PLCs, etc.
•
Radiated Noise:
Electromagnetic waves noise throughout the radio bandwidth radiated from the drive and cables.
•
Conducted Noise:
Noise generated by the drive and emitted to through the power lines.
•
Induced Noise:
Noise generated by electromagnetic induction can affect control signal lines.
Take the following measurements to prevent noise causing malfunction of other drives or devices:
• Install all components on a well grounded metal plate.
• Keep the motor cable as short as possible.
• Use noise filters on the input side of the drive to reduce conducted noise.
• Install noise filters on the input and output side of the drive, install the drive in a metal enclosure panel and use a
shielded motor cable to reduce radiated noise.
• Use shielded motor and control circuit lines and lay control circuit lines at least 30 cm away from power lines in order
to prevent malfunction due to induced noise.
A – Power supply
C – AC reactor
B – MCCB
D – Drive
A – Power supply
C – Drive
B – MCCB
D – DC Reactor
B
A
C
D
R/L1
U
V
W
X
Y
Z
S/L2
T/L3
Commo
n̲
TMonly
A
C
D
R/L1
B
S/L2
T/L3
1
+
2
+
Commo
n̲
TMonly
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...