5.10 o: Operator Related Settings
YASKAWA EUROPE
SIEP
YASKAWA AC Drive L1000V Technical Manual
153
5
Setting 0: Forward
Setting 1: Reverse
u
o3: Copy Function
These parameters control the Copy function of the optional LCD operator (JVOP-180). The Copy function stores
parameter settings into the memory of the digital operator to facilitate the transfer of those settings to other drives that are
the same model, capacity, and same control mode setting. Refer to
Copy Function Related Displays on page 185
for a
description of errors and displays.
n
o3-01 Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
0: Copy Select (no function)
1: INV --> OP READ
Copies all parameters from the drive to the digital operator.
Note:
The copy protection for the digital operator is enabled by default. Set o3-01 to 1 to unlock copy protection.
2: OP --> INV WRITE
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
3: OP<-->INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
n
o3-02 Copy Allowed Selection
Allows and restricts the use of the Copy function.
0: Disabled
1: Enabled
u
o4: Maintenance Monitor Settings
n
o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note:
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h
will also be displayed in monitor U4-01.
n
o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in U4-01.
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless if the motor is running or not.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Up/Down command is active (even if the
motor is not rotating) and when there is voltage output.
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
No.
Name
Setting Range
Default
o3-02
Copy Allowed Selection
0 or 1
0
No.
Name
Setting Range
Default
o4-01
Cumulative Operation Time Setting
0 to 9999 H
0 H
No.
Name
Setting Range
Default
o4-02
Cumulative Operation Time Selection
0 or 1
1
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...