5.4 d: Reference Settings
YASKAWA EUROPE
SIEP
YASKAWA AC Drive L1000V Technical Manual
117
5
5.4
d: Reference Settings
The d parameters determine the speed of the elevator including the speed reference and Field Forcing settings for motor
response.
u
d1: Speed Reference
The d1 parameter group is used to set the speed reference. Switch the multi-function input contact terminals to create a
multi-step speed sequence using the various references set to the d1 parameters.
n
d1-01 to d1-08: Speed References 1 to 8
These parameters set speed references 1 through 8. Each of these speed reference values can be selected using digital
inputs programmed for multi-speed selection (H1-
= 3, 4, 5).
Refer to
Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3) on page 86
n
d1-18: Speed Reference Selection Mode
Sets the priority of the speed reference inputs.
Setting 0: Use multi-speed references d1-01 to d1-08
Up to eight separate preset speed references can be programmed to the drive using parameters d1-01 through d1-08 and
can be selected using binary coded digital inputs. When d1-18 is set to “0”, parameters d1-19 through d1-23 are not
displayed. Refer to
Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3) on page 86
for details.
Setting 1: High speed reference has priority
Six different speeds (d1-19 to d1-23, d1-26) can be programmed to the drive and can be selected using dedicated digital
inputs. Each of the speed references set to d1-19 through d1-23 takes priority over the leveling speed set to d1-26. When
d1-18 is set to “1”, parameter d1-01 to d1-08 are not displayed. Refer to
Separate Speed Inputs (d1-18 = 1 or 2) on
Setting 2: Leveling speed reference has priority
Six different speeds (d1-19 to d1-23, d1-26) can be programmed to the drive and can be selected using dedicated digital
inputs. The leveling speed reference in d1-26, however, takes priority over all other speed references when enabled via
one of the multi-function input terminals (H1-
= 53). When d1-18 is set to “2”, parameters d1-01 to d1-08 are not
Separate Speed Inputs (d1-18 = 1 or 2) on page 86
n
d1-19: Nominal Speed
Sets the nominal speed when a multi-function input terminal is programmed for “Nominal speed” (H1-
= 50).
No.
Parameter Name
Setting Range
Default
d1-01 to d1-08
<1> Setting units and the default setting are determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit Selection (o1-
for details.
Speed Reference 1 to 8
0.00 to 120.00 Hz
0.00 Hz
No.
Parameter Name
Setting Range
Default
d1-18
Speed Reference Selection Mode
0 to 2
1
No.
Name
Setting Range
Default
d1-19
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit
for details.
Nominal Speed
0.00 to 120.00 Hz
50.00 Hz
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...