5.8 L: Protection Functions
148
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
Setting 2: Enabled for Entire Frequency Range
The carrier frequency is reduced at the following speeds:
• At or below 6 Hz when output current exceeds 100% of drive rated current.
• Above 6 Hz when output current exceeds 112% of drive rated current.
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back
to its normal value.
n
L8-40: Carrier Frequency Reduction Off-Delay Time
Sets the delay time which is used to switch back to the normal carrier frequency. The carrier frequency reduction function
is disabled if this value is 0 s.
n
L8-41: High Current Alarm Selection
The drive can be set to trigger a high current alarm (HCA) when the output current rises too high.
Setting 0: Disabled
No alarm is triggered.
Setting 1: Enabled
An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output indicating an
alarm (H2-
= 10) can be programmed.
n
L8-43: Output Phase Loss Detection Time
Sets the amount of time that an Output Phase Loss condition has to be present before a fault is triggered.
n
L8-88: Safe Disable Operation Mode
Determines the operation performed by the drive when the Safe Disable input is activated.
Setting 0: Mode 0
Setting 1: Mode 1 (L7 compatible)
When the Safe Disabled Input is triggered, the operator displays and alarm, and the corresponding output terminal will
react as follows:
No.
Name
Setting Range
Default
L8-40
Carrier Frequency Reduction Off-Delay Time
0.00 to 2.00 s
0.50 s
No.
Name
Setting Range
Default
L8-41
High Current Alarm Selection
0 or 1
0
No.
Name
Setting Range
Default
L8-43
Ouput Phase Loss DetectionTime
0.0 to 2.0 s
0.5 s
No.
Name
Setting Range
Default
L8-88
Safe Disable Operation Mode
0 or 1
1
L8-88
Safe Disable Operation
Selection
Alarm Display during Safety Disable
Alarm Output (H2-
= 10 )
Drive Ready
(H2-
= 6)
0 (mode 0)
Hbb
ALM flashes
ON
OFF
1 (mode1)
Hbb
ALM flashes
OFF
ON
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...