6.3 Fault Detection
176
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
The brake control circuit does not work properly.
Ensure the motor brake operates properly with a brake control command from the drive.
Digital Operator Display
Fault Name
UL3
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Cause
Possible Solution
Parameter settings are not appropriate for the load.
Check the settings of parameters L6-02 and L6-03.
There is a fault on the machine side.
Check the load for any problems.
Digital Operator Display
Fault Name
UL4
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06).
Cause
Possible Solution
Parameter settings are not appropriate for the load.
Check the settings of parameters L6-05 and L6-06.
There is a fault on the machine side.
Check the load for any problems.
Digital Operator Display
Fault Name
Uv1
DC Bus Undervoltage
One of the following conditions occurred while the drive was stopped:
• Voltage in the DC bus fell below the undervoltage detection level (L2-05)
• For 200 V class: approximately 190 V
• For 400 V class: approximately 380 V (350 V when E1-01 is less than 400)
Cause
Possible Solution
Input power phase loss.
• The main circuit drive input power is wired incorrectly.
• Correct the wiring.
One of the drive input power wiring terminals is loose.
• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.
Refer to Wire Gauges and Tightening Torque on
There is a problem with the voltage from the drive input
power.
• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main circuit magnetic contactor.
The power has been interrupted.
Correct the drive input power.
The main circuit capacitors are worn.
• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
The relay or contactor on the soft-charge bypass circuit
is damaged.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
Digital Operator Display
Fault Name
Uv2
Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.
Cause
Possible Solution
Control power supply wiring is damaged.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the control board, the entire drive, or the control power supply. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.
Internal circuitry is damaged.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
Digital Operator Display
Fault Name
Uv3
Soft-Charge Bypass Circuit Fault
The soft-charge bypass circuit failed.
Cause
Possible Solution
The relay or contactor on the soft-charge bypass circuit
is damaged.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
Digital Operator Display
Fault Name
voF
Output Voltage Detection Error
Problem detected with the voltage on the output side of the drive.
Cause
Possible Solution
Hardware is damaged.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or a Yaskawa
representative.
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...