B.3 Parameter Table
YASKAWA EUROPE
SIEP
YASKAWA AC Drive L1000V Technical Manual
231
B
u
H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
n
H1: Multi-Function Digital Inputs
No.(Addr.)
Name
Description
Setting
Page
H1-03
(400H)
<19> With the speed reference priority d1-18 set to 0, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7 are: 24,
13, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F respectively.
Terminal S3 Function Selection
Assigns a function to the multi-function digital inputs.
Refer to page
to page
for a description of setting values.
Note:
Unused terminals should be set to F.
Min: 3
Max: 79
H1-04
(401H)
Terminal S4 Function Selection
Min: 3
Max: 79
H1-05
(402H)
Terminal S5 Function Selection
Min: 3
Max: 79
H1-06
(403H)
Terminal S6 Function Selection
Min: 3
Max: 79
H1-07
(404H)
Terminal S7 Function Selection
Min: 3
Max: 79
H1 Multi-Function Digital Input Settings
H1-
Setting
Function
Description
Page
3
Multi-Step Speed Reference 1
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
terminals will create a multi-step speed sequence using the speed references set in d1-01 through d1-08.
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
7
Accel/decel Ramp Selection 1
Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in C1-03, C1-04).
When combined with another input terminal set for "Accel/Decel ramp 2" (H1-
= 1A), the drive can also
switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in C1-07, C1-08).
8
Baseblock Command (N.O.)
Closed: No drive output
9
Baseblock Command (N.C.)
Open: No drive output
F
Not Used (Through Mode)
Select this setting when using the terminal in a pass-through mode. The terminal does not trigger a drive function
but can be used as digital input for the controller the drive is connected to.
14
Fault Reset
Closed: Resets faults if the cause is cleared and the Up/Down command is removed.
15
Emergency Stop (N.O.)
Closed: Decelerates to stop at the Emergency Stop ramp set to C1-09.
17
Emergency Stop (N.C.)
Open: Decelerates to stop at the Emergency Stop ramp set to C1-09.
18
Timer Function Input
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2-
= 12).
1A
Accel/decel Ramp Selection 2
Used in conjunction with an input terminal set for “Accel/decel ramp selection 1” (H1-
= 7), and allows the
drive to switch between accel/decel ramp 3 and 4.
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...