5.7 H: Terminal Functions
128
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
Setting 2: Speed agree 1 (f
ref
/f
out
Agree 1)
Closes whenever the actual output speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the current speed
reference regardless of the direction.
Note:
Detection works in both directions, forward and reverse.
Figure 5.13
Figure 5.13 Speed Agree 1 Time Chart
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 140
Setting 3: User-set speed agree 1 (f
ref
/f
set
Agree 1)
Closes whenever the actual output speed or motor speed (CLV, CLV/PM) and the speed reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
Note:
Detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.14
Figure 5.14 User Set Speed Agree 1 Time Chart
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 140
Setting 4: Speed Detection 1
Output opens when the output speed rises above the detection level set in L4-01 plus the detection width set in L4-02.
The terminal remains open until the output speed falls below the level set in L4-01.
Note:
Detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Status
Description
Open
Output speed or motor speed does not match the speed reference while the drive is running.
Closed
Output speed or motor speed is within the range of speed reference ±L4-02.
Status
Description
Open
Output speed or motor speed and the speed reference are not both within the range of L4-01 ±L4-02.
Closed
Output speed or motor speed and the speed reference are both within the range of L4-01 ±L4-02.
Status
Description
Open
Output speed or motor speed exceeded L4-01 + L4-02.
Closed
Output speed or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
L4-02
L4-02
Speed
reference
Speed agree 1
ON
OFF
Output speed
or motor speed
User Set
Speed Agree 1
OFF
ON
Speed
reference
OFF
ON
Speed
reference
Output
speed
L4-01
+/- L4-02
L4-01
+/- L4-02
Output speed
or motor speed
common̲TMo
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...