B.3 Parameter Table
YASKAWA EUROPE
SIEP
YASKAWA AC Drive L1000V Technical Manual
235
B
u
L: Protection Functions
L parameters provide protection to the drive and motor, including control during momentary power loss, Stall
Prevention, frequency detection, fault reset, overtorque detection, torque limits, and other types of hardware protection.
n
L1: Motor Protection
n
L2: Undervoltage Detection
n
L3: Stall Prevention
n
L4: Speed Detection
No. (Addr.)
Name
Description
Setting
Page
L1-01
(480H)
<5> Default setting is determined by the control mode (A1-02).
Motor Overload Protection
Selection
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
Min: 0
Max: 5
L1-02
(481H)
Motor Overload Protection Time
Sets the motor thermal overload protection (oL1) time.
Default: 1.0 min
Min: 0.1 min
Max: 5.0 min
L1-13
(46DH)
Continuous Electrothermal
Operation Selection
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
No. (Addr.)
Name
Description
Setting
Page
L2-05
(489H)
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<15> Default setting value is dependent on the setting for the input voltage (E1-01).
Undervoltage Detection Level
(Uv)
Sets the DC bus undervoltage trip level.
Default:
Min: 150 Vdc
Max: 210 Vdc
No. (Addr.)
Name
Description
Setting
Page
L3-01
(48FH)
<16> The setting value is dependent on the setting for the carrier frequency reduction (L8-38).
Stall Prevention Selection during
Acceleration
0: Disabled.
1: General purpose. Acceleration is paused as long as the current is above the L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without exceeding the L3-02 level.
Default: 1
Min: 0
Max: 2
L3-02
(490H)
Stall Prevention Level during
Acceleration
Used when L3-01 = 1 or 2. 100% is equal to the drive rated current.
Min: 0%
Max: 165%
L3-03
(491H)
Stall Prevention Limit during
Acceleration
Sets the lower limit for Stall Prevention during acceleration as a percentage of drive rated
current.
Default: 50%
Min: 0%
Max: 100%
L3-05
(493H)
Stall Prevention Selection during
Run
0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss.
1: Decel time 1. Uses the deceleration ramp set to C1-02 while Stall Prevention is performed.
2: Decel time 2. Uses the deceleration ramp set to C1-04 while Stall Prevention is performed.
Default: 1
Min: 0
Max: 2
L3-06
(494H)
Stall Prevention Level during Run
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current.
Min: 30%
Max: 165%
No. (Addr.)
Name
Description
Setting
Page
L4-01
(499H)
Speed Agreement Detection Level
L4-01 sets the speed detection level for digital output functions H2-
= 3, 4, 5.
L4-02 sets the hysteresis or allowable margin for speed detection.
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
L4-02
(49AH)
Speed Agreement Detection Width
Default: 2.0 Hz
Min: 0.0 Hz
Max: 20.0 Hz
L4-03
(49BH)
Speed Agreement Detection Level
(+/-)
L4-03 sets the speed detection level for digital output functions H2-
= 13, 14, 15, 16.
L4-04 sets the hysteresis or allowable margin for speed detection.
Default: 0.0 Hz
Min: –120.0 Hz
Max: 120.0 Hz
L4-04
(49CH)
Speed Agreement Detection Width
(+/-)
Default: 2.0 Hz
Min: 0.0 Hz
Max: 20.0 Hz
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
common_
TMonly
V/f
OLV
common_
TMonly
V/f
OLV
All Modes
common_
TMonly
All Modes
common_
TMonly
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...