170
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
6.3 Fault Detection
6.3
Fault Detection
u
Fault Displays, Causes, and Possible Solutions
Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal MA-MB-
MC. Remove the cause of the fault and manually clear the fault before attempting to run the drive again.
Table 6.7 Detailed Fault Displays, Causes, and Possible Solutions
Digital Operator Display
Fault Name
CF
Control Fault
The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV Control.
Cause
Possible Solution
Motor parameters are improperly set.
Check the motor parameter settings and repeat Auto-Tuning.
Torque limit is too low.
Set the torque limit to the most appropriate setting (L7-01 through L7-04).
Load inertia is too big.
• Adjust the deceleration ramp (C1-02, -04, -06, -08).
• Set the speed reference to the minimum value and interrupt the Up/Down command when the drive finishes decelerating.
Digital Operator Display
Fault Name
CoF
Current Offset Fault
The current detection circuit is damaged, or there was residual induction voltage in the motor (such as during sudden deceleration
or when coasting) when the drive attempted to start the motor.
Cause
Possible Solution
While the drive automatically adjusted the current
offset, the calculated value exceeded the allowable
setting range.
• Create a motor restart sequence that allows enough time for residual induction voltage to dissipate
• Lengthen the active deceleration ramp (C1-02, -04, -06, -08)
Digital Operator Display
Fault Name
or
CPF00 or CPF01
Control Circuit Error
Cause
Possible Solution
There is a self diagnostic error in control circuit.
• Cycle power to the drive.
• Set the frequency to the minimum value and interrupt the Run command when the drive finishes decelerating.
Connector on the operator is damaged.
• Replace the operator.
Digital Operator Display
Fault Name
CPF02
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Cause
Possible Solution
Control circuit is damaged.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
Digital Operator Display
Fault Name
CPF03
Control Board Connection Error
Connection error between the control board and the drive
Cause
Possible Solution
There is a connection error.
• Turn off the power and check the connection between the control board and the drive
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
Drive fails to operate properly due to noise interference.
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or on the drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise and use surge absorbers if required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power supply input.
Digital Operator Display
Fault Name
CPF06
EEPROM Memory Data Error
An error in the data saved to EEPROM
Cause
Possible Solution
There is an error in EEPROM control circuit.
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
The power supply was switched off while parameters
were being saved to the drive.
Reinitialize the drive (A1-03).
Power to the control board was lost while writing
parameter settings during Rescue Operation.
Reinitialize the drive (A1-03).
Digital Operator Display
Fault Name
CPF07
Terminal Board Connection Error
CPF08
Cause
Possible Solution
There is a faulty connection between the terminal board
and control board.
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...