4.16 Diagnostics and interrupt
Via the parametrization you may activate a diagnostic interrupt for the module. With a
diagnostics interrupt the module serves for diagnostics data for diagnostic interrupt
incoming
.
As soon as the reason for releasing a diagnostic interrupt is no longer present, the diag-
nostic interrupt
going
automatically takes place. Within this time window (1. diagnostic inter-
rupt
incoming
until last diagnostic interrupt
going
) the MF-LED of the module is on.
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
ERR_A
1
Diagnostic
00h
01h
2F01h
02h
MODTYP
1
Module information
18h
03h
ERR_C
1
reserved
00h
04h
ERR_D
1
reserved
00h
05h
CHTYP
1
Channel type
72h
06h
NUMBIT
1
Number diagnostics bits per
channel
08h
07h
NUMCH
1
Number channels of the
module
04h
08h
CHERR
1
Channel error
00h
09h
CH0ERR
1
Channel-specific error
00h
0Ah
CH1ERR
1
Channel-specific error
00h
0Bh
CH2ERR
1
Channel-specific error
00h
0Ch
CH3ERR
1
Channel-specific error
00h
0Dh
CH4ERR…
CH7ERR
4
reserved
00h
0Eh ... 11h
DIAG_US
4
µs ticker (32bit)
00h
13h
Byte
Bit 7 ... 0
0
n
Bit 0: set at module failure
n
Bit 1: set at internal error
n
Bit 2: set at external error
n
Bit 3: set at channel error
n
Bit 6 ... 4: reserved
n
Bit 7: set at error in parametrization
Diagnostic data
ERR_A Diagnostic
VIPA System SLIO
Deployment
Diagnostics and interrupt
HB300 | FM | 054-1CB00 | en | 18-06
94