For the VIPA
SPEED7 Studio
and the Siemens SIMATIC Manager there is the block FB
321 - ACYC_DS for simplified access available.
More information about the usage of this block may be found in the
manual "SPEED7 Operation List" from VIPA.
4.14 Scaling and units
n
As a "normalization" for position, velocity and acceleration, you can specify a
Gear
factor
‘0x8180-02 - Gear factor’ on page 116
in the object dictionary. This gear
factor represents
units
in thousands with the rotary axis makes exactly one revolution.
Positive direction of rotation is turning to the right (clockwise) with view towards the motor
flange.
n
All currents are normalized to the unit [mA].
n
[User] is a user-defined unit, which depends on the
Gear factor
.
4.15 Monitoring and error reaction
4.15.1
Overview
The System SLIO motion module has monitor functions. The monitoring works in 3 steps:
n
1. Limitation
–
‘0x8100-04 - Limit active bits’ on page 113
–
Limitations within the normal operating range, adapted to the respective applica-
tion.
n
2. Warning
–
‘0x8100-05 - Warnings active bits’ on page 114
–
The permissible operating range is almost exhausted and the system is about to
initiate a fault response.
n
3. Error
–
‘0x8100-06 - Error active bits’ on page 115
–
The permissible operating range is exceeded and a configurable fault response is
automatically triggered.
–
Error messages are also shown via
‘0x8100-02 - Status word’ on page 110
CAUTION!
Please consider that incorrectly set monitoring functions can cause dam-
ages to persons and materials!
The voltage of DC 24V module power supply and the internal control voltage of the output
stages are monitored. If the voltage over or under runs the limit values, a warning or error
‘0x8100-02 - Status word’ on page 110
. On an error, there is an error
reaction of the motion module, which can be configured.
Scaling and units
Direction of rotation
Current unit
General
Voltage monitoring
VIPA System SLIO
Deployment
Monitoring and error reaction > Overview