Basic Installation Procedures
975-1057-01-01
24
Size of AC Input Wiring
Wire size must be coordinated with the overcurrent
protection provided ahead of the wire involved, in
accordance with the electrical codes or regulations
applicable to your installation.
Therefore, the wiring used between the AC input
circuit breaker and the inverter/charger input must
be sized to match the input breaker rating.
Split phase
Dual input
Breaker Size
Used
30 amps per
line
30 amps per
line
Wire Size
No. 10 AWG
No. 6 AWG
Color Coding
L1
: black:
N
: white
L2
: red
Gnd
: green
L1
: red or black
N
: white
L2
: red or black
Gnd
: green
Table 2 AC Wire Size In and Out of the
Inverter/Chargers
For dual input, the wire may be red or black;
consult the documentation provided with the AC
source (utility or generator).
Size of AC Output Wiring
Wire size must be coordinated with the current the
wiring will carry. This current may be determined
by the 25-amp maximum inverter current, or by the
bypass current, which is determined by the
overcurrent protection provided ahead of the
Freedom SW-RVC.