Basic Installation Procedures
975-1057-01-01
26
Suitability
This automatic neutral-to-ground bonding system
requires AC input sources with bonded neutral.
This will be the case in most situations: in a utility
feed, at an external AC hook-up, or a generator
with a bonded neutral. If not, have an electrician
look into bonding the source’s neutral to ground.
See also
General AC Wiring Considerations on
.
DC Components
Batteries
The Freedom SW-RVC system requires a 12-
volt, lead-acid deep-cycle battery or group of
batteries to provide the DC current that the
inverter/charger converts to AC power. The
battery may be a Flooded, Gel, or AGM type.
See
Battery Sizing Example on page 68
for
information on:
n
Estimating the battery size that will meet
your requirements.
n
Designing battery banks.
n
Restrictions on the size of appliances.
For information on cabling and hooking up
batteries, see
Battery Cabling and Connections
.
For detailed information about specific brands
of batteries, consult individual battery
manufacturers.
DC Cabling
Definition
DC cabling includes all of the cables and
connectors between the batteries, the DC
disconnect and overcurrent protection device,
and the inverter/charger.
Type
All installations require multi-strand insulated
cables. The DC cables must be copper and
must be rated 75 °C minimum.