Basic Installation Procedures
975-1057-01-01
50
Step 7: Performing Checks Prior to
Initial Start-Up
Before testing your installation, ensure these conditions are met:
n
Chassis and AC grounds are properly installed.
n
AC input connections and AC output connections are wired
correctly on the terminal block and not reversed.
n
Positive (+) battery cable is connected to the positive (+)
battery terminal through the DC fuse and disconnect switch
or DC circuit breaker.
n
Negative (–) battery cable is connected to the negative (–)
battery terminal.
n
Battery voltage is within the proper range for this unit: 10–16
volts DC
n
DC disconnect switch or breaker is turned off.
n
AC input and output breakers are turned off.
n
All connections are tight.