7.2 Overtemperature
This message indicates a malfunction if the interior
temperature has exceeded 70 °C. At a normal room
temperature with normal air circulation the unit is
suited for continuous operation. In case of overtem-
perature increase the air ventilation or change the
operation site. In case of this malfunction the gas
supply of the burner will be shut off automatically.
Overtemperature
Fig. 7.2/1
7.3 BHC time limit active
This message indicates that the time limit
(30 seconds) was turned on due to a clogged
burner head. For cleaning the burner head
(see paragraph 6.2 & 9.1).
In the event that the BHC display is blinking (see
paragraph 6.2), all burning times longer than 30
seconds are auto-
matically reduced to
30 seconds. In the
event of an auto-
matic reduction in
the burning time,
the fault symbol is
displayed after the
burning operation.
To switch off the BHC time limit (see paragraph 5.1).
BHC time limit
Fig. 7.3/1
Clean burner head (6)
Fig. 7.3/2
Check burner head (6) for
clogging
7.4 Burner head assembly monitor
This message indicates that the burner head is
removed. Further operation is possible after the
burner head is reinstalled.
Burner head assembly
Fig. 7.4/1
7.5 [Fuego pro] Tilt sensor
If the burner is tilt for more than 90° (e.g. when
changing rechargeable batteries), the burner
deactivates itself automatically and the "tilt sensor"
symbol is shown in the display for a couple of
seconds.
Tilt sensor
Fig. 7.5/1