If there is a usual gas trip and the ECS parameter “vent valve active mode” is OFF, or if there is
a gas trip with automatic inerting request, or if there is an engine shutdown, the iGPR control
system automatically starts the steps that follow:
•
Closes the shut-off valves (CV7285C, CV7291C, CV7292C).
•
Opens the vent valves (CV7289C, CV7286C, CV7287C).
•
Opens the pressure regulating valve (CV7288C).
•
Closes the master shut-off valve of the FGSS (controlled by PCS).
•
Opens the vent valve of the FGSS (controlled by PCS).
NOTE:
The pressure in the engine gas piping and in the iGPR decreases to
atmospheric pressure (degassing state).
•
If there is a gas trip with automatic inerting request, the iGPR control system starts the
automatic inerting sequence, refer to
.
6.6.4
Gas trip with automatic inerting
A gas trip with automatic inerting is necessary in the conditions that follow:
•
Emergency gas trip switches are active
•
Gas trip from gas detection system is active
•
Incorrect gas inlet conditions
•
Ventilation failure of the double wall pipes.
In these conditions the iGPR control system automatically starts the steps that follow:
•
Closes the master shut-off valve of the FGSS.
•
Opens the vent valve of the FGSS.
•
Closes the shut-off valves (CV7285C, CV7291C, CV7292C).
•
Opens the vent valves (CV7289C, CV7286C, CV7287C).
•
Opens the pressure regulating valve (CV7288C).
NOTE:
The pressure in the engine gas piping and in the iGPR decreases to
atmospheric pressure.
The automatic inerting sequence then starts, refer to
.
6.6.5
Automatic inerting sequence
The automatic inerting sequence has the steps that follow:
•
The engine safety system (ESS) sends a signal to the iGPR control system.
•
The iGPR control system opens the inert valve in the FGSS.
•
Inert gas flows through the pipes from the inert valve in the FGSS to the inert gas release
outlet of the engine.
•
The inert valve in the FGSS closes again after 25 seconds, when the pipes are filled with
inert gas.
•
If the inerting sequence was successful, the iGPR control system activates the inerting
completed signal from iGPR to PCS.
X92DF
AA00-8904-00AAA-043A-A
Operation Manual
Integrated gas pressure regulation
Winterthur Gas & Diesel Ltd.
- 286 -
Issue 002 2020-08
Содержание X92DF
Страница 18: ...X92DF Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 18 Issue 002 2020 08...
Страница 147: ...X92DF Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 147 Issue 002 2020 08...
Страница 253: ...X92DF Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 253 Issue 002 2020 08...
Страница 425: ...7 Installation 7 1 Installation 426 X92DF Operation Manual Winterthur Gas Diesel Ltd 425 Issue 002 2020 08...