Starts step 2 (automatic leakage test):
○
Activates the leakage test active signal from iGPR to PCS and ECS.
•
Pressurizes the iGPR piping.
•
Monitors the pressure drop in the iGPR piping.
○
Activates the leakage test OK signal from iGPR to PCS and ECS.
○
Deactivates the leakage test active signal from iGPR to PCS and ECS.
•
Starts step 3 (flushing):
○
Activates the flushing active signal from iGPR to PCS and ECS.
○
Opens the shut-off valve (CV7285C).
○
Closes the vent valve at the engine inlet (CV7289C).
○
Opens the pressure regulating valve (CV7288C).
○
Opens the shut-off valves (CV7291C, CV7292C) and the vent valves (CV7286C,
CV7287C).
○
Activates the flushing OK signal from iGPR to PCS and ECS.
○
Deactivates the flushing active signal from iGPR to PCS and ECS.
•
Starts step 4 (pressurization and stabilisation):
○
Activates the pressure stabilisation active signal from iGPR to PCS and ECS.
○
Closes the vent valves (CV7286C, CV7287C)
○
Starts the pressurization and stabilisation.
○
Activates the pressure stabilisation OK signal from iGPR to PCS and ECS.
○
Deactivates the pressure stabilisation active signal from iGPR to PCS and ECS.
○
Activates the transfer preparation OK signal from iGPR to PCS and ECS.
NOTE:
The ECS uses this signal to start the GAV operation.
NOTE:
If one of the transfer preparation steps is not successful, the iGPR control
system sends a gas trip signal to the PCS and ECS. Then the iGPR control
system changes to degassing state, refer to
6.6.2
Overpressure release state
The iGPR control system automatically starts the steps that follow, if the gas pressure is 0.5 bar
above the setpoint value:
•
Opens the vent valve (CV7289C) as long as necessary.
•
Controls the pressure regulating valve (CV7288C).
6.6.3
Shutdown on gas operation
The iGPR control system automatically starts different steps related to the conditions.
If you manually start a transfer to diesel operation (refer to section
), or if there is a usual gas trip and the ECS parameter “vent valve active mode” is ON,
the iGPR control system automatically starts the steps that follow:
•
Closes the shut-off valves (CV7285C, CV7291C, CV7292C).
•
Opens the vent valves (CV7289C, CV7286C, CV7287C).
•
Opens the pressure regulating valve (CV7288C).
NOTE:
The pressure in the engine gas piping decreases to atmospheric pressure.
X92DF
AA00-8904-00AAA-043A-A
Operation Manual
Integrated gas pressure regulation
Winterthur Gas & Diesel Ltd.
- 285 -
Issue 002 2020-08
Содержание X92DF
Страница 18: ...X92DF Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 18 Issue 002 2020 08...
Страница 147: ...X92DF Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 147 Issue 002 2020 08...
Страница 253: ...X92DF Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 253 Issue 002 2020 08...
Страница 425: ...7 Installation 7 1 Installation 426 X92DF Operation Manual Winterthur Gas Diesel Ltd 425 Issue 002 2020 08...