Installation and electrical connection
en
Installation and operating instructions Wilo-SiFire FIRST
15
ƒ
For the jockey pump, thermal overload protection is provided. The overload protec-
tion is installed in the switchgear for the jockey pump. Set overload protection to the
rated current of the jockey pump shown on the rating plate.
ƒ
Do
not
provide protection against low water!
ƒ
Systems with diesel motors: The switchgear controls the operating parameters of
the diesel motor. Alarm signals are signalled on the switchgear. Additional informa-
tion can be found in the chapter “Switchgear for diesel motors”.
6.4
Installation
DANGER
Danger of falling into wells and basins!
Open wells and water tanks for the water supply are located near the system. Danger
of falling. Cover open basins or attach a safety harness during installation.
DANGER
Diesel motor: Risk of personal injury due to inadvertent start!
The system with diesel motor has two starter batteries. This makes it possible for
the system to be activated inadvertently. Danger of serious injuries! Check that the
batteries are disconnected before installation. If the batteries are not disconnected,
have the batteries disconnected by a qualified electrician.
DANGER
Risk of fatal injury due to dangerous lone working practices!
Work in chambers and narrow rooms as well as work involving risk of falling are dan-
gerous work. Such work may not be carried out autonomously! A second person
must be present for safety reasons.
WARNING
Hand and foot injuries due to lack of protective equipment!
Danger of (serious) injuries during work. Wear the following protective equipment:
• Safety gloves for protection against cuts
• Safety shoes
• Safety helmet must be worn if lifting equipment are used!
NOTICE
Use only properly functioning lifting equipment!
Use only properly functioning lifting equipment to lift and lower the pump. Ensure
that the pump does not become jammed during lifting and lowering. Do
not
exceed
the maximum bearing capacity of the lifting equipment! Check that lifting equip-
ment is functioning properly before use!
NOTICE
Installations for sprinkler systems
The systems are used for fire protection. Installation and electrical connection must
be carried out in accordance with EN 12845 and the local regulations!
6.4.1
Operating modes
Operate the systems in accordance with EN 12845:
ƒ
Inlet mode
ƒ
Suction mode
If possible, operate the system in inlet mode. If inlet mode is not possible, operate the
system in suction mode.