en
Electric pump switchgear
44
WILO SE 2020-12
ƒ
Global alarm - Activates the output assigned to this function.
ƒ
Alarm type A - Activates the output assigned to this function.
ƒ
Alarm type B - Activates the output assigned to this function.
ƒ
Siren - Activates the output assigned to this function, with the modes defined in
menu M06 Audible alarms.
ƒ
Sir.04 - If the siren has been silenced and the alarm is still active after 4 hours, the
acoustic alarm will be reactivated.
ƒ
Sir.24 - If the siren has been silenced and the alarm is still active after 24 hours, the
acoustic signal will be reactivated.
ƒ
In Motorcycle - Alarm enabled only when the motor is running.
ƒ
Inhibit - The alarm can be temporarily disabled by activating a programmable input
with the Inhibit alarm function.
ƒ
Modem - A modem connection is made with the modes foreseen by the relative set-
up data set.
ƒ
No LCD - The alarm is managed normally but is not shown on the display.
Enabled
Retentive
Global
Type A
Type B
Siren
Sir.04
Sir.24
Running
Inhibit
Modem
No LCD
CODE
DESCRIPTION
DEFAULT ALARM PROPERTIES
A01
Low mains voltage
•
•
•
•
•
•
A02
High voltage grid
•
•
•
•
•
•
A03
Low network frequency
•
•
•
•
•
•
A04
High frequency network
•
•
•
•
•
•
A05
Mains voltage asymmetry
•
•
•
•
•
•
A06
Phase failure
•
•
•
•
•
•
A07
Incorrect phase sequence
•
•
•
•
•
•
A08
Failure to start the pump
•
•
•
•
•
•
•
•
A09
Locked rotor
•
•
•
•
•
•
•
•
A10
Dry running
•
•
•
•
•
•
•
•
A11
Current too low
•
•
•
•
•
•
•
•
A12
Current too high
•
•
•
•
•
•
•
•
A13
Unbalanced currents
•
•
•
•
•
•
•
•
A14
Unexpected current
•
•
•
•
•
•
A15
Wrong CT connection
•
•
•
•
•
•
A16
System error xx
•
•
•
•
•
•
A17
Low pump room temperature
•
•
•
•
•
•
A18
High local pump temperature
•
•
•
•
•
•
A19
Water reserve
•
•
•
•
•
A20
Low tank level
•
•
•
•
•
A21
Empty tank
•
•
•
•
•
A22
Low priming tank level
•
•
•
•
•
A23
System not in automatic mode
•
•
•
•
•
A24
Electric pump in operation
•
•
•
•
•
•
A25
Non-pressure pump
•
•
•
•
•
A26
Pressure pump
•
•
•
•
•
A27
Maintenance request 1
•
•
•
•
•
•
A28
Maintenance request 2
•
•
•
•
•
•
A29
Maintenance request 3
•
•
•
•
•
•
A30
Partially open suction valve
•
•
•
•
•
•
•
Содержание Wilo-SiFire FIRST