Electric pump switchgear
en
Installation and operating instructions Wilo-SiFire FIRST
47
Function
Description
Keypad lock
Locks the operation of the front keyboard, excluding page navigation keys.
Silencing siren
Disables the siren.
Alarm inhibition
If activated, it allows to disable the alarms with the property "Alarm Inhibition" activated
Reset alarms
Reset of the alarm whose triggering condition has ceased
Command menu Cxx
Executes the command menu command defined by the index parameter (x).
STOP button
Closing the input is equivalent to pressing the STOP key.
RESET button
Closing the input is equivalent to pressing the RESET key.
TEST inhibition
Prevents automatic test execution
LED test
Turns on all LEDs on the front panel (lamp test).
Automatic stop enable
When closed, it enables the automatic motor stop parameter P02.16. To comply with EN 12845
this input must be deactivated.
Pump pressure switch
When the input is activated it indicates that the pump is under pressure.
Partially open suction valve
With input activated, it signals alarm A30 Partially open suction valve.
Delivery valve partially open
With input activated, it signals alarm A31 Partially open delivery valve.
Sprinkler activated
With input activated, it signals alarm A32 Sprinkler pump room in operation.
Pilot pump (jockey) active
With input activated, it signals that the pilot pump is started.
Pilot pump failure
With input active, it signals that the pilot pump in the pump room is not working (e.g. thermal
trip).
Drainage pump failure
With active input it signals that the drainage pump in the pump room is not able to operate (e.g.
thermal trip).
Flood valve
With active input it signals the active deluge valve
OFF mode
With active input, the pump control outputs are opened and further starts are inhibited.
Test valve
With active input, it signals alarm A39 Test valve open.
Modbus writing inhibited
With active input, it inhibits write commands via Modbus.
Default input functions
Input
Function
INP1
Starting pressure switch
INP2
Solicitation float
INP3
Automatic start lock
INP4
Pilot pump start control
9.5.2
Overview of output functions
The following table shows all the functions that can be associated with OUTn program-
mable digital outputs. Each output can then be set to have normal or inverted function
(NOR or REV). Some functions require an additional numeric parameter, defined with
the index (x) specified by parameter P10.n.02. See menu M10 Digital Outputs for more
details.
Function
Description
Disabled
Output disabled
Configurable
Free user configuration To be used, for example, if the output is used in a PLC logic
Line contactor
Line contactor control.
Star contactor
Star contactor command.
Triangle contactor
Triangle contactor command.
Truck contactor
Autotransformer contactor command.
Bypass contactor
Bypass contactor command.
AUT mode locked
Indicates that the automatic mode has been excluded.
Lack of tension
Indicates power failure.
Failure to start
Indicates that the motor has not started (alarm A08).
Start-up request
The pressure switches have requested the activation of the electric pump.