Installation and operating instructions Wilo-SiFire FIRST
59
M09 – Motor temperature 1
Unit
Standard
Area
P09.01
Source measure.
Specifies from which source the fuel level meas-
urement is taken. OFF= not managed. RES1 =
taken from the resistive sensor with analogue in-
put on terminal RES1. AINx = taken from the ana-
logue input of an EXP expansion module. RES
AN= taken from the resistive input of an EXP ex-
pansion module.
OFF
OFF
RES3
AINx
RES AN
P09.02
Channel number.
Channel number (x) to be specified if AINx has
been selected in the previous parameter.
1
1 … 4
P09.03
Resistive sensor type.
If a resistive sensor is used, select which curve to
use. Characteristic curves can be set freely using
the Xpress software.
VDO
VDO / DATCON / VEGLIA /
MURPHY
P09.04
Resistive sensor offset.
If a resistive sensor is used, it allows to add or re-
move an offset in Ohm to the set the curve to
compensate, for example, the cable length. This
value can also be set without entering setup us-
ing the quick function in the command menu
which allows you to see the measurements while
performing calibration.
Ohm
0
-30.0 … +30.0
P09.05
MAX Pre-alarm temperature
°
90
20-300
P09.06
MAX Alarm limit temperature
°
100
20-300
P09.07
MIN Alarm limit temperature
°
OFF
OFF/ 20-300
P09.08
Heater activation threshold
°
OFF
OFF/ 20-300
P09.09
Heater deactivation threshold
°
OFF
OFF/ 20-300
P09.10
Faulty temperature sensor alarm delay
Min.
OFF
OFF/1–60
M10 – Motor temperature 2
Unit
Standard
Area
P10.01
Source measure.
Specifies from which source the fuel level meas-
urement is taken. OFF= not managed. RES2 =
taken from the resistive sensor with analogue in-
put on terminal RES2. AINx = taken from the ana-
logue input of an EXP expansion module. RES
AN= taken from the resistive input of an EXP ex-
pansion module.
OFF
OFF
RES3
AINx
RES AN
P10.02
Channel number.
Channel number (x) to be specified if AINx has
been selected in the previous parameter.
1
1 … 4
P10.03
Resistive sensor type.
If a resistive sensor is used, select which curve to
use. Characteristic curves can be set freely using
the Xpress software.
VDO
VDO / DATCON / VEGLIA /
MURPHY
P10.04
Resistive sensor offset.
If a resistive sensor is used, it allows to add or re-
move an offset in Ohm to the set the curve to
compensate, for example, the cable length. This
value can also be set without entering setup us-
ing the quick function in the command menu
which allows you to see the measurements while
performing calibration.
Ohm
0
-30.0 … +30.0
P10.05
MAX Pre-alarm temperature
°
90
20-300
P10.06
MAX Alarm limit temperature
°
100
20-300