Electric pump switchgear
48
WILO SE 2020-12
Function
Description
Motorcycle pump
Indicates that the pump is started.
Global alert
Output activated in the presence of any alarm with global alarm properties activated.
Siren
Power supply to the alarm siren.
Remote alarms
Pulsed output for communication with the FFLRA unit when performed in digital I/O mode
Room temperature heater
Controls the output of the room heater, driven by room temperature
Type A failure
Fire alarm.
Type B failure
Technical fault alarm.
Device failure
Output normally energised. De-energises for system errors (all) or if microprocessor is not in con-
trol
Local ventilation
Output energised when pump room temperature is close to A18 (3 degrees lower) alarm. Stops
when the temperature has fallen below the threshold for 1 minute.
PLC(x)
Output controlled by PLCx flag.
REM(x)
Output controlled by remote variable REMx.
Interactive whiteboard (x)
Output controlled by LIM(x) limit threshold status.
TIMx
Output controlled by TIMx timer variable.
Partially open suction valve
Output active if the inlet function is programmed Partially open inlet valve and this inlet is active.
Delivery valve partially open
Output active if the inlet function is programmed Partially open inlet valve and this inlet is active.
Sprinkler activated
Output active if the Sprinkler input function is programmed and this input is active.
Drainage pump failure
Output active if the drain pump failure input function is programmed and this input is active.
Low pump room temperature
Output energised when alarm A17 Pump room temperature too low is active.
Pilot pump failure (jockey)
Output active if pilot pump failure input function is programmed and this input is active.
AUTOMATIC TEST start
This output is activated during the first 20 seconds of the automatic test, see parameter P07.01
Axx
Output energised when alarm Axx is active (xx = 1 ... number of alarms)
UAx
Output energised when user alarm UAx is active.
Default output functions
Output
Function
OUT1
Line contactor
OUT4
Lack of tension
OUT5
Failure to start
OUT6
Motorcycle pump
OUT9
Start-up request
9.6
Command menu
The command menu allows you to perform occasional operations such as zeroing
measurements, counters, alarms, etc. If you have entered the password for advanced
access, then you can also use the command menu to perform automatic operations
useful for configuring the instrument. The following table shows the functions available
with the command menu, divided according to the level of access required.
CODE
COMMAND
ACCESS
DESCRIPTION
C01
Reset maintenance interval 1
User
Resets the MNT1 maintenance alarm and recharges the
maintenance counter at the set hours.
Maintenance can only be reset if all the following condi-
tions have occurred in the previous hours:
ƒ
the motor must be started;
ƒ
opening of the pressure switch;
ƒ
no active alarm excluding the maintenance alarm.
C02
Reset maintenance interval 2
User
As above, referring to MNT2.
C03
Reset maintenance interval 3
User
As above, referring to MNT3.
C04
Partial engine hour meter reset
User
Resets the partial hour meter of the electric pump to zero.
C05
Reset generic CNTx counters
User
Resets the generic CNTx counters