en
Switchgear of diesel pump
56
WILO SE 2020-12
and
keys. A bar graph will also be displayed indicating the setting range, the
minimum possible values, the previous value and the default value.
ƒ
Pressing
+
sets the value to the minimum possible and pressing
+
sets the maximum possible. Pressing
+
simultan-
eously returns the setting to the default value.
When entering text, use the
and
keys to select the alphanumeric char-
acter and use
and
to move the cursor within the text. Pressing
+
simultaneously positions the alphanumeric selection directly on the "A" char-
acter.
ƒ
Press
to return to parameter selection. The value entered remains stored.
ƒ
Press
STOP
to save the changes and exit the settings. The switchgear performs a re-
set and returns to normal operation. If no keys are pressed for 2 consecutive
minutes, the setup menu is automatically exited and the system returns to normal
operation without saving parameters.
You can make a back-up copy to the EEPROM memory, for keyboard editable set-up
data only. These can be restored to the working memory. Backup and restore data com-
mands are available in the command menu.
10.3
Overview of the most important
parameters
The controller is programmed and preset at the factory for fully automatic operation.
However, some of the main parameters contained in the respective menus are:
M01 – Utilities
Unit
Standard
Area
P01.01
Language – Language selection for the texts on
the display
English
English
Italian
French
Spanish
German
P01.02
Power on clock setup - Activate automatic access
to clock setup after power up
OFF
OFF - ON
P01.03
Display contrast - Adjusting the contrast of the
LCD display
%
50
0-100
P01.04
High display backlight intensity
%
100
0-100
P01.05
Low display backlight intensity
%
25
0-50
P01.06
Low backlighting transition delay
S
180
5-600
P01.07
Return to default page - Delay in resetting the
default page display. If set to OFF the display al-
ways remains on the last manually selected page
S
300
OFF/10-600
P01.08
Default page - Default page shown on the display
at power on and after the delay.
Global
(pages list)
P01.09
Motor pump description
FFL
String 20 char.
These parameters are accessible with user level passwords.
M02 – General
Unit
Standard
Area
P02.01
Rated motor speed
S
1.0
0.0-60.0
P02.02
Temperature unit of measurement
°C
°C / °F