Electric pump switchgear
en
Installation and operating instructions Wilo-SiFire FIRST
45
Enabled
Retentive
Global
Type A
Type B
Siren
Sir.04
Sir.24
Running
Inhibit
Modem
No LCD
A31
Delivery valve partially open
•
•
•
•
•
•
•
A32
Local sprinkler pumps in operation
•
•
•
•
•
•
•
A33
Maximum number of pilot pump
starts
•
•
•
•
•
•
•
A34
Pilot pump failure
•
•
•
•
•
•
•
A35
Maximum pilot pump time
•
•
•
•
•
•
•
A36
Drainage pump failure
•
•
•
•
•
•
•
A37
Communication error
•
•
•
•
•
•
A38
Pressure switch test error
•
•
•
•
•
•
A39
Test valve open
•
•
•
•
•
•
•
A40
Power too low
•
•
•
•
•
•
•
•
A41
Power too high
•
•
•
•
•
•
•
•
UA1
User Alarm 1
•
…
…
UA8
User Alarm 8
•
9.4.1
Description of alarms
CODE
DESCRIPTION
CAUSE
A01
Low mains voltage
Mains voltage below the threshold set in P05.01.
A02
High voltage grid
Grid voltage above the threshold set in P05.02.
A03
Low network frequency
Grid frequency below the threshold set in P05.03.
A04
High frequency network
Grid frequency above the threshold set in P05.04.
A05
Mains voltage asymmetry
Grid voltage asymmetry higher than the threshold set in P05.05.
A06
Phase failure
Lack of one of the phases.
A07
Incorrect phase sequence
Incorrect phase sequence.
A08
Failure to start the pump
The motor has not started with a current greater than 10% of the rated current in the times
defined in the M05 menu or the input programmed with the pump pressure switch function
has not closed.
A09
Locked rotor
Motor current higher than 500% of the rated for a time longer than 5s.
A10
Dry running
Pump runs with vacuum. Measured power factor lower than the threshold set in P05.13
A11
Current too low
The motor current is below the threshold set in P05.06.
A12
Current too high
The motor current is higher than the threshold set in P05.07.
A13
Unbalanced currents
The maximum current asymmetry threshold set in P05.14 has been exceeded.
A14
Unexpected current
The printed circuit board detects a current greater than 5 % of the I
n
even though it has no
influence on the motor start
A15
Wrong CT connection
One or more current transformers are not connected correctly (negative active power is
measured). Check the connections at terminals 57, 58, 59, 60
A16
System error xx
Internal error. Contact Technical Support
A17
Low pump room temperature
The pump room temperature is below the threshold set in P04.02 for longer than P04.03.
A18
High local pump temperature
The pump room temperature is above the threshold set in P04.04 for longer than P04.05.
A19
Water reserve
Alarm generated by the input programmed with the Water Reserve function.
A20
Low tank level
Water level in the tank below the threshold set in P02.18.
A21
Empty tank
Water level in the tank below the threshold set in P02.19.