Switchgear of diesel pump
58
WILO SE 2020-12
M07 – Motor speed
Unit
Standard
Area
P07.01
W/Pick-up motor speed measurement mode.
Selects the source from which to take the motor
speed measurement.
OFF = speed not displayed and controlled.
Pick-up LF = speed measured by low sensitivity
pick-up sensor.
Pick-u HF = as receding, with high sensitivity. See
technical characteristics at the end of the manual.
Pick-up LCD LF = speed measured by low-sensit-
ivity pick-up sensor. Speed measurement is used
only for rpm display. Pick-up LCD HF = as above,
with high sensitivity input.
To comply with EN 12845, this setting must
NOT be left "OFF"!
High Freq
OFF
Low Freq
High Freq
LCD Low Freq
LCD High Freq
P07.02
RPM / W- pick-up ratio.
Ratio between rpm and frequency of the W or
pick-up signal. Can be set manually or automati-
cally by following this procedure: From the
STARTING IN SERVICE page, with the motor run-
ning at rated speed, press the left and right arrow
keys simultaneously for 5 seconds. The system
will acquire the current speed as the nominal one,
using the current frequency of the W/pick-up to
calculate the value of parameter P07.02.
1,000
0.001-50.000
P07.03
MAX speed limit for alarm A26
%
110
100-120
P07.04
Delay MAX. speed alarm for alarm A26
S
3.0
0.5-60.0
P07.05
MIN speed limit for alarm A25
%
90
80-100
P07.06
Delay MIN. Speed alarm for alarm A25
S
5
0-600
M8 – Oil pressure
Unit
Standard
Area
P08.01
Source measure.
Specifies from which source the fuel level meas-
urement is taken. OFF= not managed. RES3 =
taken from the resistive sensor with analogue in-
put on terminal RES3. AINx = taken from the ana-
logue input of an EXP expansion module. RES
AN= taken from the resistive input of an EXP ex-
pansion module.
OFF
OFF
RES3
AINx
RES AN
P08.02
Channel number.
Channel number (x) to be specified if AINx has
been selected in the previous parameter.
1
1 … 4
P08.03
Resistive sensor type.
If a resistive sensor is used, select which curve to
use. Characteristic curves can be set freely using
the Xpress software.
VDO
VDO / DATCON / VEGLIA /
MURPHY
P08.04
Resistive sensor offset.
If a resistive sensor is used, it allows to add or re-
move an offset in Ohm to the set the curve to
compensate, for example, the cable length. This
value can also be set without entering setup us-
ing the quick function in the command menu
which allows you to see the measurements while
performing calibration.
Ohm
0
-30.0 … +30.0
P08.05
Pressure measuring unit
Bar
bar/psi
P08.06
MIN Pre alarm pressure
bar/psi
3.0
0.1-180.0
P08.07
MIN pressure alarm limit
bar/psi
2.0
0.1-180.0