Switchgear of diesel pump
en
Installation and operating instructions Wilo-SiFire FIRST
57
M02 – General
Unit
Standard
Area
P02.03
Start delay from pressure switch
S
1.0
0.0-60.0
P02.04
Delayed departure from priming float
S
1.0
0.0-60.0
P02.05
Waiting time automatic stop from priming float
S
OFF
OFF/1 … 10000
P02.06
Rated aux voltage
VAC
230
100-240
P02.07
Minimum aux voltage threshold
%
75
OFF/50-100
P02.08
Maximum aux voltage threshold
%
120
100-130/OFF
P02.09
Aux voltage alarm delay
S
30
0-600
P02.10
Waiting time automatic stop from pressure
switch
S
OFF
OFF/0…10000
P02.15
Analogue AINx channel for water level monitoring
in the storage tank
OFF
OFF/1-4
P02.16
Low water level threshold in the tank
%
20
0-100
P02.17
Treshold for water level in cooling circuit
%
10
0-100
P02.18
Water level threshold for
S
60
0…10000
P02.19
Maximum number of pilot starts
OFF
OFF/0…10000
P02.20
Maximum pilot pump operating time
Min.
OFF
OFF/1…1000
P02.21
Alarm delay A56-A57 .
S
60
1-1000
M03 – PASSWORD
Unit
Standard
Area
P03.01
Enabling password for menu access
OFF
OFF –
ON (PRESET)
P03.02
User level password
1000
0-9999
P03.03
Advanced level password
2000
0-9999
P03.04
Remote access password
OFF
OFF/1-9999
M04 – Ambient temperature
Unit
Standard
Area
P05.01
Room temperature reading -Defines the source
from which the room temperature measurement
is taken. OFF = measurement disabled. INT =
measurement from sensor incorporated in the
control unit. EXT = temperature measurement
taken from NTC remote probe connected to ter-
minals 53 and 54.
INT
OFF
INT
EST
P05.02
Minimum temperature alarm threshold for alarm
A46
°
4
0-70
P05.03
Minimum temperature alarm delay for alarm A46
S
10
0-600
P05.04
Maximum temperature alarm threshold for alarm
A47
°
40
0-160
P05.05
Maximum temperature alarm delay for alarm A47
S
10
0-600
P05.06
Room heater start threshold
°
8
0-70
P05.07
Room heater stop threshold
°
10
0-70
P05.08
Heater start/stop delay
S
10
0-600
M05 – Batteries
Unit
Standard
Area
P05.01
Rated battery voltage
V
12
12/24
P05.02
MAX voltage limit
%
130
110-140
P05.03
MIN voltage limit
%
75
60-130
P05.04
MIN/MAX voltage delay
S
10
0-120
P05.05
Battery boost interval
H
168
1-1000
P05.06
Battery boost duration
Min.
60
1-240