Installation and electrical connection
en
Installation and operating instructions Wilo-SiFire FIRST
17
6.4.1.2
Suction mode
max. 3.2 m
2/3
1/3
>1 m
R = >2.5xØ
Ø = min. 80 mm
4xØ
>2xØ
MIN
MAX
Qmax. 1.5 m/s
Fig. 5:
Example of installation: Suction mode
ƒ
The centre line of the pump must not be located more than 3.2 m above the lowest
water level in the water tank.
ƒ
Suction line diameter: min. 80 mm.
ƒ
Flow rate in the suction line: max. 1.5 m/s at maximum volume flow.
ƒ
Provide a separate suction line for each pump. The suction lines must not be con-
nected to each other!
ƒ
Install a foot valve at the lowest point in the suction line.
ƒ
Install a suction strainer upstream of the foot valve:
–
Diameter: at least 1.5 times the nominal diameter of the suction line
–
Grain/particle size: max. 5 mm
–
The suction strainer must be able to be cleaned without draining the water tank.
ƒ
Install one automatic priming device per pump:
–
The priming device consists of: break tank, pipe with non-return valve descend-
ing to the discharge side of the pump.
–
Break tank, pump and suction line must always be filled with water.
NOTICE! Also
ensure that the water level is maintained in the event of a leakage in the foot
valve!
When the water level in the break tank goes down to 2/3 of the normal water
level, start the pump.
NOTICE! If the pump does not start up, trigger an alarm at
a constantly monitored location!