Functions Common to All the Control Modes
CFW500 | 11-5
11
Description:
Voltage level to activate the DC link voltage regulation.
P0152 – Gain Proportional to the DC Link Voltage Regulator
Adjustable
Range:
0.00 to 9.99
Factory
Setting:
1.50
Properties:
Access Groups
via HMI:
MOTOR
Description:
Gain proportional to the DC link voltage regulator.
When the option of P0150 is 1 or 3, the value of P0152 is multiplied by the DC link voltage “error”, that is, error =
current DC link voltage – P0151. The result is directly added to the inverter output frequency in Hz. This resource
is normally used to prevent overvoltage in applications with eccentric loads.
to
show the block diagrams and example graphs.
Ramp
Reference
Output frequency
error
≥ 0
+
-
hold
P0001
P0004
P0151
P0002
P0100-P0104
Figure 11.2:
Block diagram DC link voltage limitation – Ramp Hold
U
d
rated
DC link voltage (P0004)
F0022-
Overvoltage
DC Link
Regulation
Time
Time
U
d
P0151
Output
frequency
Figure 11.3:
Example graph of DC link voltage limitation – Ramp Hold
Содержание CFW500 V1.8X
Страница 2: ......
Страница 4: ......
Страница 8: ...Contents...
Страница 34: ...General Information 2 4 CFW500...
Страница 38: ...About the CFW500 3 4 CFW500 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW500 4...
Страница 52: ...Programming Basic Instructions 5 10 CFW500 5...
Страница 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Страница 76: ...Available Motor Control Types 8 4 CFW500 8...
Страница 84: ...V f Scalar Control 9 8 CFW500 9...
Страница 170: ...Communication 17 8 CFW500 17...