11 FUNCTIONS COMMON TO ALL THE CONTROL MODES
This chapter describes the functions common to the inverter V/f and V V W control modes, but which interferes
in the drive performance.
11.1 RAMPS
The inverter ramp functions allow the motor to accelerate or decelerate faster or slower. They are adjusted by
parameters that define the linear acceleration time between zero and the maximum speed (P0134) and the time
for a linear deceleration from the maximum speed to zero.
In the CFW500, three ramps with different functions were implemented:
1
st
Ramp – standard for most functions.
2
nd
Ramp – it may be activated by the user, according to the drive requirement, by means of the inverter
command word or by a digital input.
3
rd
Ramp – it is used for the inverter protection functions, such as: Current Limitation, DC Link Control, Quick
Stop, etc. The 3
rd
Ramp has priority over the other ramps.
NOTE!
The setting with too short ramp time may cause overcurrent in the output (F0070), undervoltage
(F0021) or overvoltage (F0022) of the DC link.
P0100 – Acceleration Time
Adjustable
Range:
0.1 to 999.0 s
Factory
Setting:
10.0 s
Properties:
Access Groups
via HMI:
BASIC
Description:
Acceleration time from zero to maximum speed (P0134).
P0101 – Deceleration Time
Adjustable
Range:
0.1 to 999.0 s
Factory
Setting:
10.0 s
Properties:
Access Groups
via HMI:
BASIC
Description:
Deceleration time from maximum speed (P0134) to zero.
Содержание CFW500 V1.8X
Страница 2: ......
Страница 4: ......
Страница 8: ...Contents...
Страница 34: ...General Information 2 4 CFW500...
Страница 38: ...About the CFW500 3 4 CFW500 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW500 4...
Страница 52: ...Programming Basic Instructions 5 10 CFW500 5...
Страница 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Страница 76: ...Available Motor Control Types 8 4 CFW500 8...
Страница 84: ...V f Scalar Control 9 8 CFW500 9...
Страница 170: ...Communication 17 8 CFW500 17...