Explanation of Function
Seite 95 / 180
Start frequency
This frequency is the value the operator must set before the Inverter will give an
output.
Mainly used when an operator adjusts the start torque.
By setting the start frequency higher, direct starting is caused and the starting current increases. Therefore
an overload is within the restriction range and the inverter has a tendency to trip on over-current protection.
Function
code
Set range
Description
b082
0.10 to 9.99
Units:Hz
Reduced voltage start selection
This function is to raise the voltage slowly on motor starting.
The lower this value the more torque is available on starting..
However, by making this value lower, the inverter has a tendency of tripping on
over-current protection, because of almost direct starting.
Function
code
Data
Time to take for reduced
voltage starting
00
No reduced voltage start
b036
01
06
Short (about 6ms)
Long (about 36ms)
FW
Output frequency
Output voltage
Starting frequency
b082
00 01
06
---
b082:Start frequency
Relation
FW
Output frequency
Output voltage
b082
b036:Reduced voltage
start selection
b082:Start frequency
Relation code
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...