Installation and Wiring
Seite 18 / 180
2.1.1 Installation
1. Transportation
This inverter has plastic parts. So handle with care.
Do not over tighten the wall mounting fixings as the mountings may crack, causing is a risk
of falling.
Do not install or operate the inverter if there appears to be damage or parts missing.
2. Surface for Mounting of Inverter
The temperature of the Inverter heatsink can become very high (the highest being about
150ºC). The
surface, which you are mounting the Inverter onto, must be made of a non-flammable
material (i.e steel) due to the possible risk of fire. Attention should also be made to the air
gap surrounding the Inverter. Especially when there is a heat source such as a breaking
resistor or a reactor.
3. Operating Environment - Ambient Temperature
The ambient temperature surrounding the Inverter should not exceed the allowable
temperature range
(usually -10 to 50ºC).
The temperature should be measured in the air gap surrounding the Inverter, shown in the
diagram
above. If the temperature exceeds the allowable temperature, the component life will
become shortened
especially in the case of the Capacitors.
4.Operating Environment - Humidity
The humidity surrounding the Inverter should be within the limit of the allowable
percentage range
(usually 5% to 90%). Under no circumstances should the Inverter be in an environment
where there is
the possibility of moisture entering the Inverter.
Also avoid having the Inverter mounted in a place that is exposed to the direct sunlight.
Keep the space enough not to
be
prevented the ventilation of
5cm or more
5cm or more
10cm or
10cm or more
Inverter
Inverter
Flow of the air
Wall
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...