Explanation of Function
Seite 174 / 180
5.6 Capacitor Life Curve
(Note1)
Ambient temperature means the surrounding temperature of the inverter. In case the inverter is
installed in a cabinet, ambient temperature is the temperature of the internal air of the cabinet.
(Note2)
DC bus capacitors are recommended to be replaced every 5 years. And if the inverter is used in a
worse condition, this recommended replacing period is reduced.
10
20
30
40
1
Ambient
50
0
-1
2
3
4
5
6
7
8
9
10
Life time (year)
12h day operation
24h/day operation