Explanation of Function
Seite 67 / 180
(2) Start, End of O2-L terminal
Set item
Functio
n code
Data Contents Notes
O2 start
A111
-400.-400. Unit : Hz Set starting frequency
O2 end
A112
-400.-400. Unit : Hz Set ending frequency
O2 start
rate
A113 -100.-100.
Unit : % Set starting rate for output frequency
command –10-10V (Notes)
O2 end rate
A114
-100.-100.
Unit : % Set ending rate for output frequency
command –10-10V(Notes)
(Example
3)
(Notes) The rates of –10V-10V is following.
-10V- 0V:-100-0%
0V-10V:0-100%
For example, in case of use with O2-L terminal, set -50% to A113,
50% to A114.
Forward
Maximum
frequency
Reverse
frequency
A111
A114
A113
A112
+10V
-10V
(Example 3)