Explanation of Function
Seite 63 / 180
00
Always ON
This function is effective on acceleration, constant
speed, deceleration.
01
Always OFF
This function is ineffective on acceleration, constant
speed, deceleration.
A081
02
On decelerating
OFF
This increases a loss of motor and reduces the energy
regenerated to inverter on decelerating.
Maximum frequency
Set the maximum frequency value of the inverter.
This set value is the maximum frequncey that the inverter will achieve when
It receives top speed reference from the control terminals or the digital operator.
To the change the 1
st
/2
nd
/3
rd
maximum frequency, set an intelligent input terminal to 08(SET)/17(SET3) and
switch the input ON.
The Inverter output voltage from the base frequencey to the maximum frequency is the same level as the
voltage selected on the motor voltage selection.
Function
code
Limit of
setting
Contents
A004/A204
A304
30.-400.
Unit : Hz
Carrier frequency
The carrier frequency of the PWM wave-form output from the inverter is adjustable
by changing b083.
If the carrier frequency is set higher, the audible noise from motor will be reduced
but the RFI noise and the leakage current may be increased.
This function may help to avoid the resonant frequency of the motor or the mechanical system.
Functio
n code
Limit of setting
Contents
b083
0.5-15.0
(Note1)
Unit:kHz
(Note1) The maximum value of the carrier frequency in order to achieve full output current is different
depending on the capacity. When raising the carrier frequency, the rated output current will be reduced.
Voltage class
200V class
400V class
Contents
Maximum
carrier
frequency
Derating on carrier
frequency = 15kHz
Maximum
carrier
frequency
Derating on carrier
frequency = 15kHz
1.5kW
15 100% 15 100%
2.2kW
15 100% 15 100%
Output
Maximum frequency
Base frequency
Motor Voltage
selection
100
)
A004/A204/A304: 1
st
/2
nd
/3
rd
maximum frequency
Relation
b083:Carrier frequency
Relation
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...