Explanation of Function
Seite 112 / 180
A044/A244/A
344
: Control method
C001 - C008 : Intelligent input selection
H005/H205
: Speed response
H050/H250
: PI proportion gain
H051/H251
: PI integration gain
H052/H252
: P proportion gain
H070
: PI proportion gain for
it hi
A044/A244/A
344
: Control method
C001 - C008 : Intelligent input selection
H005/H205
: Speed response
H050/H250
: PI proportion gain
H051/H251
: PI integration gain
H052/H252
: P proportion gain
H070
: PI proportion gain for
CONTROL GAIN SWTCH FUNCTION (CAS)
When sensorless vector control, 0Hz sensorless vector control,
or vector control with sensor is selected in control method, this
function can set and change two kinds of gain ,time constant in
speed control system. (proportion, integration compensation)
When control gain switching is selected in intelligent input
selection, gain which is set to H50, H250, H51, H251, H52,
H252 is selected if signal OFF, and gain which is set to H70,
H71, H72 is selected if signal ON.
When control gain switching is not selected in intelligent input selection, same gain is selected as gain in case of signal OFF.
Setting item
Function code
Setting range
contents
Control method selection
A044/A244/A3
44
03
04
05
SLV (A344 is not)
0 Hz domain SLV (A344 is not)
V2 (A344)
Intelligent input selection
C001 - C008
26
CAS : control gain switching
Speed response
H005/H205
0.01 - 99.99
Unit : no dimension
PI proportion gain
H050/H250
1.0 - 999.9/1000
Unit : %
PI integration gian
H051/H251
1.0 - 999.9/1000
Unit : %
P proportion gain
H052/H252
1.0 - 999.9/1000
Unit : %
PI proportion gain for
switching
H070
1.0 - 999.9/1000
Unit : %
PI integration gain for
switching
H071
1.0 - 999.9/1000
Unit : %
P proportion gain for
switching
H072
1.0 - 999.9/1000
Unit : %
P / PI SWITCHING FUNCTION(PPI)
When sensorless vector control, 0 Hz domain sensorless vector,
or control vector with sensor is selected in control method,
this function can change and use control (compensation) method
of speed control system to proportion integration compensation
and proportion compensation.
When P / PI switching is selected in intelligent input selection,
proportion integration compensation is selected if signal is OFF,
and proportion compensation is selected if signal is ON.
When P/PI switching is not selected in intelligent input selection, proportion integration compensation is available.
Relation code
Relation code
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...