Explanation of Function
Seite 147 / 180
Connect each inverter in parallel as shown below. It is necessary to short terminals RP and SN on the last
inverter in the link (even if communication is to only one inverter the link should still be made).
By shorting between RP and SN, the terminal resistance is increased and controls the reflection of the signal.
(2) Setting
The following settings are required to operate RS485 communication.
Set item
Function
code
Set value
Description
02 Operator
03 RS485
04 Option
1
Data command
C070
05 Option
2
02 Loop-back
test
03 2400
bps
04 4800
bps
05 9600
bps
Communicating
transmission
speed
C071
06 19200
bps
Communication
code
C072 1
to32
This assigns the station number of the
inverter. This is used when you control
more than one simultaneously.
7 7
bit
Communication bit
C073
8 8
bit
00 No
parity
01 Even
parity
Communication
parity
C074
02 Odd
parity
1 1
bit
Communication bit
C075
2 2
bit
Communication
waiting time
C078
0 to 1000 Units :ms
SP SN RP SN
SP SN RP SN
External
control
machine
_ _ _
SP SN RP SN
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...