Explanation of Function
Seite 62 / 180
Base frequency
Base frequency and motor voltage
AVR function
(1) Base frequency and motor voltage
On selection of base frequency and motor voltage, set the output of the inverter (frequency voltage) to the
motor rating.
The Base frequency is the nominal frequency of the motor, this value can be found on the nameplate of the
motor. It is
important
to match the Base frequency (A003) to this nominal value or there is risk of damage to
the motor.
If a motor has a base frequency higher than 60Hz, it is considered to be a special motor. In this situation, it
is important to make sure the maximum output current of the inverter is higher than the FLC of the motor.
The Motor Voltage Selection is the nominal voltage of the motor, this value can be found on the nameplate of
the motor. It is
important
to match the Motor Voltage (A082) to this nominal value or there is risk of damage
to the motor.
When changing second base frequency (A203) / third base frequency(A303) an intelligent input terminal
must be set to 08(SET) / 17(SET3) and switched on.
Setting item
Function
code
Setting limit
Contents
Base
frequency
A003/A203
A303
30.-1
st
/2
nd
/ 3
rd
maximum
frequency
Unit:Hz
200/215/220/230/240
Unit:V When inverter is 200V
class, selection is possible.
380/400/415/440/460/480
Unit:V When inverter is 400V
class, selection is possible.
Motor
voltage
selection
A082
575/600
Unit:V When inverter is 600V
class,selection is possible.
(2) AVR function
Even if the incoming voltage changes, this function will keep the output voltage and a constant voltage level.
The output voltage to the motor in this function references to the voltage selected on motor voltage selection.
Select Yes/No of this function on A081 AVR selection.
Function
code
Data Contents
Description
A003/A203/A303: 1
st
/2
nd
/3
rd
base frequency
A081: AVR selection
A082 M t
lt
l ti
Relation code
Output
Motor voltage
selection(%)
Output
frequency
Base frequency
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...