Explanation of Function
Seite 116 / 180
(2) Specification of the alarm relay output terminal
The specifications of the alarm relay output terminal is a changeover contact. Action is as follows.
Example on using as alarm
State of output
terminal
C036
Set value
Power
source
State of
inverter
AL1-AL
0
AL2-AL
0
On abnormal Close Open
On
On normal
Open Close
00
(a
contact)
Off -
Open
Close
On abnormal Open
Close
On
On normal
Close
Open
01
(b
contact)
Off
-
Open
Close
AL
AL1 AL2
Inverter
Resistor load Inductor load
Maximum
AC250V, 2A
DC30V, 8A
AC250V,
0.2A
DC300V,
0.6A
AL1-AL
0
Minimum
AC100V, 10mA
DC5V, 100mA
M i
AC250V, 1A
DC30V 1A
AC250V,
0 2A
AL2 AL
Contact Specification