Explanation of Function
Seite 101 / 180
Jogging operation
This function can be used to rotate the motor in small steps to allow
fine-tuning.
Set an intelligent input terminal to 06(JG).
(1) Jogging frequency
The jogging operation does not use acceleration, therefore it would be advisable to set the jogging frequency
to limit the starting current to a minimum or tripping may occur. Adjust A038 to the jogging frequency
required.
Functio
n code
Data Description
A038
0.0, start frequency-9.99
Units:Hz
(2) Jogging operation selection
Functio
n code
Data Description
Jogging operation during run
Valid / Invalid
00
Free-run on jogging stop
01
Decelerating stop on jogging stop.
02
Direct braking on jogging stop.
Invalid (example1)
(notes)
03
Free-run on jogging
stop.(example2)
04
Decelerating stop on jogging stop.
A039
05
Direct braking on jogging stop.
Valid (example2)
(notes)
(Note) When using the jogging function, turn FW terminal or RV terminal ON after the JG terminal is turned
ON.
(It is the same when the operation command point is from the operator.)
A038
: Jogging frequency
A039
: Jogging selection
C001 C008
I t lli
t
Relation code
JG
FW
RV
Output frequency
A038
Free-run
JG
FW
JG
FW
(Example1)
(Example2)
Frequency command
Frequency command
When setting of A039 is 00,01 or 02 and
FW terminal is turned ON beforehand,
When setting of A039 is 03,04 or 05 and
FW terminal is turned ON beforehand,
Содержание V3000-015HF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...