WAGO-I/O-SYSTEM 750
Parameterizing
85
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
8.6.14
Increase_Swing_Back
Table 52: 2.2.3 Increase_Swing_Back
Parameter address Function
Access Factory default
setting
15
Increase_Swing_Back
R/W
0x0000
Bit 0 ... 7: Increase_Swing_Back [0 ... 255]
This value is indicated as a percentage at a resolution of 10% within a range of 0 to 2550% for
extending a swing-back drive during positioning.
0 ... 255:
0 ... 2550% - Percentage of extension of the swing-back drive at a resolution
of 10%
0:*
Extending the swing-back drive by 0%
Bit 7 ... 15: Reserved
* Default settings