WAGO-I/O-SYSTEM 750
Device Description
23
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
Pos: 20.24 /Alle Serien (Allgemeine M odul e)/Überschriften/Ebene 2/T echnische D aten - Überschrift 2 @ 3\mod_1232967587687_21.docx @ 26924 @ 2 @ 1
3.5
Technical Data
Pos: 20.25 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Technische D aten/Sonder kl emmen/T echnische D aten 750- 0636/000-700 @ 18\mod_1391516987379_21.docx @ 144390 @ 333333 @ 1
3.5.1
Device Data
Table 1: Technical Data ‒ Device
Width
12 mm
Height (from upper edge of 35 DIN rail) 64 mm
Depth
100 mm
Weight
50 g
3.5.2
Power Supply
Table 2: Technical Data ‒ Power Supply
Voltage supply
Via system voltage terminal bus
(5 V DC) and power jumper contacts
(24 V DC)
Current consumption system voltage
max.
(5 V DC)
55 mA
Current consumption power jumper
contacts
max.
(24 V DC)
10 mA
Voltage via power jumper contacts
24 V DC (-15 % ... +20 %)
Current via power jumper contacts
max.
10 A
Motor supply voltage
UA typ.
20 V DC … 28 V DC
Low voltage/overvoltage are monitored
Low voltage switching threshold U
A typ.
19 V DC
Threshold for overvoltage error.
“Overload” diagnostic bit is set.
Both outputs are activated during
overvoltage. This corresponds to the
“Brake” status. This switching threshold
is above the maximum operating
voltage of 27.5V and can be exceeded
by switching residual inductances. This
might also occur in motor mode when
the brake ramp is set to short.
29 V DC
Current consumption U
A
typ.
2 mA + Load
Isolation
500 V system/supply
3.5.3
Communication
Table 3: Technical Data ‒ Communication
Data width (internal bus)
1 x 32 bit data, 2 x 8 bit control/status