Example 16 "ShutDown_Distance is reached in phase P2":
Figure 26: Example 16, "ShutDown_Distance is Reached in Phase P2"
The waypoint that starts phase 4, which is defined by the ShutDown_Distance, is
reached before phase P2 is completed. In this example, phase P2 may be
terminated prematurely.
Example 17 "ShutDown_Distance is reached in phase P1":
Figure 27: Example 17, "ShutDown_Distance is Reached in Phase P1"
The waypoint that is supposed to start phase P4 is already in phase P1. However,
since it is not allowed to interrupt the start ramp for the soft start, phase P4 may
only be started after the elapse of the configured RampTime_START. Phases P2
and P3 are skipped.
Small distance between start and setpoint position!
If the distance between the start and setpoint position is smaller than the real
reachable distance due to the runtimes of RampTime_START and
RampTime_STOP, phase P4 is also skipped!