60
Process Image
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
7.3
Extended Status Bytes
Table 23: Extended Status Byte S2
Extended Status Byte S2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
24V_
Motor_OK
Param
_Write
_Failed
Motion
Detection
Timeout
Overload 24V_OK
Overflow
_Warn
ing
Overtemp
erature
Overtempe
rature
_Warning
Overtemperature
_Warning
The temperature of the module electronics has reached a critical value.
0:
The temperature is below the warning threshold.
1:
The temperature has exceeded the warning threshold.
Overtemperature The temperature of the module electronics has exceeded the temperature
threshold. The I/O module has been turned off automatically.
0:
The temperature is below the turn-off threshold.
1:
The temperature has exceeded the turn-off threshold.
Overflow
_Warning
This bit is always set to logic '1' when the actual position is not in the range of
values defined by the limit values -2.147.400.000 and +2.147.400.000.
0:
The actual position is within the limit values.
1:
The actual position is outside the limit values.
24V_OK
This bit is set to logic '0' when the 24 V motor supply voltage
fails during operation.
0:
A 24 V power supply system has failed.
1:
Both 24 V power supply systems are available.
Overload
The I/O module output stage has detected an overload error.
The overload error derived from driver diagnostics occurs in the event of both
an overcurrent and an overvoltage. An overvoltage can occur if the power
supply unit can no longer compensate the energy that is fed back during the
braking phase. To protect the I/O module, the overload error is then generated
and the motor is switched to idle. Possible remedies: larger power supply
capacity, additional loads or extending the braking ramp.
0:
No overload error.
1:
Overload error.
MotionDetection
Timeout
'MotionDetectionTimeout' configures the maximum wait time until the first
incremental encoder pulse. If no pulse is detected within this wait time after the
start, the motion or positioning cycle is terminated prematurely and the related
'MotionDetectionTimeout' error bit set in the ExtendedInfos. This error bit can
only be acknowledged if the 'MoveNeg', 'MovePos' and 'Positioning' control
bits are set to 0.
0:
Pulses were received within the configured time period.
1:
No pulses were received within the configured time period.
Param_Write
_Failed
Parameterization Status
0:
Parameterization successfully completed.
1:
Wrong parameters.
24V_Motor_OK This bit is set to logic '0' when the 24 V field power supply
fails during operation.
0
The 24 V motor supply voltage has failed.
1
The 24 V motor supply voltage is available.