58
Process Image
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
Table 21: Status Byte S0
Status Byte S0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg
_Com
Error
Refer
ence_OK
Standstill
Busy
OnTarget
Move
Pos
Move
Neg
MoveNeg
This bit indicates that drive moves in negative direction.
0:
Drive does not move in negative direction
1:
Drive moves in negative direction
MovePos
This bit indicates that drive moves in positive direction.
0:
Drive does not move in positive direction
1:
Drive moves in positive direction
OnTarget
This bit indicates that the positioning process in the target window is
completed. The bit is reset when you quit the target window, independent of a
positioning process. See also chapter "Setting the I/O Module via the Parameter
Channel" > "I/O Module-Specific Parameter Data, Parameter 3
(TargetWindow)".
0:
Target window was quit.
1:
Positioning process in the target window is completed.
Busy
The bit sends back logic "1" while the command is executed. Otherwise, the bit
is "0".
0:
No command is being executed.
1:
A command is being executed.
Standstill
This bit is set to logic '1' when the I/O module detects the standstill condition or
does not detect incremental encoder pulses, independent if an actuation
command is being executed or not. More information about this topic is
available in chapter "Function Description" > "Standstill Condition".
0:
The standstill condition is not fulfilled or the I/O module receives
incremental encoder pulses.
1:
The standstill condition is fulfilled and the I/O module no incremental
encoder pulses.
Reference_OK
This bit is always set logically to '1', when a preset function was executed
successfully. It may be reset to logic '0' during operation. More information
about this topic is available in chapter "Function Description" > "Preset
Functions".
0:
Preset function not completed successfully.
1:
Preset function completed successfully.
Error
This bit indicates that there is a status/error message. To view detailed
information, set the control bit ,ExtendedInfo_ON’ (C1.2) to '1'. Extended
information is shown instead of the actual position.
0:
No status/error message.
1:
Status/error message.
Reg_Com
Register communication (see chapter "Setting the I/O Module via the Parameter
Channel" > "Register Communication").
0:
Process data communication enabled.
1:
Register communication enabled.