750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
8.6.8
TriggerMode_Inputs, Stop-Mode, DirectionReversal_Delay
Table 46: 2.2.3 TriggerMode_Inputs, Stop-Mode, DirectionReversal_Delay
Parameter address Function
Access Factory default
setting
8
TriggerMode_Inputs
Stop-Mode
DirectionReversal_Delay
R/W
0x0A37
Bit 0 ... 3: TriggerMode_Inputs
Input sensitivity of the digital inputs
Bit 0: Input sensitivity digital input E+, level sensitive
0:
Enabled LOW (break contact)
1:*
Active HIGH (make contact)
Bit 1: Input sensitivity digital input E-, level sensitive
0:
Enabled LOW (break contact)
1:*
Active HIGH (make contact)
Bit 2: Input sensitivity digital input P, edge sensitive
0:
Response to falling edge (break contact)
1:*
Response to rising edge (make contact)
Bit 3: Reserved
Bit 4 ... 7: Stop-Mode
Use these bits to configure whether the motor final stage sets the motor to idle after STANDARD,
EXCEPTION or EMERGENCY braking, or whether it short-circuits the motor windings to initiate
braking and switches to 24 V (750-636) or to the motor voltage potential U
A
(750-636/000-700).
This action is only carried out when a ramp has been selected in the corresponding Brake mode,
otherwise the Stop mode is specified by the configured brake properties (mode).
Bit 4: Stop-Mode_STANDARD
0:
Motor final stage sets motor at idle
1:*
Motor final stage decelerates
Bit 5: Stop-Mode_EXCEPTION
0:
Motor final stage sets motor at idle
1:*
Motor final stage decelerates
Bit 6: Stop-Mode_EMERGENCY
0:*
Motor final stage sets motor at idle
1:
Motor final stage decelerates
Bit 7: Reserved