8.6.12 CurrentLimit_Time, MotionDetectionTimeout
Table 50: 2.2.3 CurrentLimit_Time, MotionDetectionTimeout
Parameter address Function
Access Factory default
setting
13
CurrentLimit_Time
MotionDetectionTimeout
R/W
0x0000
Bit 0 ... 7: CurrentLimit_Time [0 ... 255]
CurrentLimit_Time determines the CurrentLimit_PWM ON time at n times 100 ms during a
positioning operation with PWM. More information about CurrentControl_PWM is available in the
chapter "Function Description" > "PWM Control during Positioning".
0:*
CurrentLimit_PWM function is disabled.
1 ... 255:
The CurrentLimit_PWM function is switched on with a
CurrentLimit_Time 100 ms ... 25.5 s at a resolution of 100 ms.
Bit 8 ... 13: MotionDetectionTimeout [0 ... 63]
MotionDetectionTimeout configures the maximum wait time until the first incremental encoder
pulse. If no pulse is detected within this wait time after the start, the moving cycle is terminated
prematurely and the MotionDetectionTimeout message is generated in the status.
0:*
Monitoring function disabled
1 ... 63:
Timeout after Start ramp 1 s ... 63 s with a resolution of 1 s
Bit 14 ... 15: Reserved
* Default settings