WAGO-I/O-SYSTEM 750
Parameterizing
67
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
8.2.2
Password Protection
To save the parameter data set User Settings (2), enter password 0x1235 into
register 31.
Resetting the password register!
The I/O module does not automatically reset passwords. Without another write
command to register 31, they will remain valid until the power down!
The parameter data set Factory Default (3) may be only modified by WAGO
Kontakttechnik GmbH & Co. KG.
8.2.3
Changing the Parameter Data Sets
Figure 42: Changing the Parameter Data Sets
8.2.3.1 Actual (1)
The parameter data set Actual (1) is changed by write access via the parameter
channel of the I/O module (register 56 and 57).
After writing the parameter data set; i.e. closing the parameter channel, the I/O
module validates the received parameters. No other checksum test is carried out in
the I/O module, e.g. data backup by CRC.
Upon a successful plausibility check, the I/O module accepts and uses the new
parameters.