30
Function Description
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
4.6
Operating Modes for Positioning
The operating modes for setting the drive are divided into basic and auto mode.
The following table illustrates the configuration conditions for the selection of the
corresponding operating mode.
Table 13: Process Image
Source
Name
Description
Configuration
parameter
Overtravel
Minimum drive distance for gearbox clearance
compensation. The sign determines the direction from
which the setpoint position is to be approached.
Configuration
parameter
Retry
Number of permitted repetitions in case of bad
positioning.
Control byte
Optimize_ON
'Optimize_ON' initializes the prestop value during
positioning for each braking process using the
determined braking distance.
Mode
Over-
travel: Retry
Optimize
_ON Description
Basis
0
0
0
Moving once to the stop or arriving at
the setpoint position If Prestop <> 0,
then it is decelerated in prestop
increments before the setpoint position.
Auto
A
0
0
1
Prestop value is updated using the
braking distance
B
0
n
0
Maximum number (n) of positioning
attempts.
(Optimize_ON = 0)
C
0
n
1
Maximum number (n) of positioning
attempts.
(Optimize_ON = 1)
D
<> 0
0
0
Moving once under consideration of the
gear backlash and the approach
direction.
(Optimize_ON = 0)
E
<> 0
0
1
Moving once under consideration of the
gear backlash and the approach
direction.
(Optimize_ON = 1)
F
<> 0
n
0
Maximum n positioning attempts while
considering the gearbox clearance and
the drive direction.
(Optimize_ON = 0)
G
<> 0
n
1
Maximum n positioning attempts while
considering the gearbox clearance and
the drive direction.
(Optimize_ON = 1)